![Parker AC30 series User Manual Download Page 252](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313252.webp)
C-39
Compliance
AC30 series Variable Speed Inverter
Solid-State Short-Circuit Protection
These devices are provided with integral Solid-State Short-Circuit (output) Protection. Branch circuit protection must be provided in accordance
with the latest edition of the National Electrical Code NEC/NFPA-70.
The following drives when fitted with UL Listed fuses are suitable for use on a circuit capable of delivering not more than:
Frame D: 5,000 RMS Symmetrical Amperes, 480V maximum
Frame E: 5,000 RMS Symmetrical Amperes, 480V maximum
Frame F: 5,000 RMS Symmetrical Amperes, 480V maximum
Frame G: 5,000 RMS Symmetrical Amperes, 480V maximum
Frame H: 10,000 RMS Symmetrical Amperes, 480V maximum
Frame J: 10,000 RMS Symmetrical Amperes, 480V maximum
Frame K: 18,000 RMS Symmetrical Amperes, 480V maximum
When fitted with UL listed, Ferraz Shawmut / Mersen, Class J, AJT type fuses, frame D, E and F sizes may be used on a supply delivering not
more 100,000 RMS Symmetrical amperes, 480V maximum.
When fitted with UL listed, Ferraz Shawmut / Mersen, Class J, AJT type fuses these may be used on frame G, for frame H & J use UL
recognized, Ferraz Shawmut/Mersen Type A50QS fuses, sizes may be used on a supply rating delivering not more than 100,000 RMS
Symmetrical amperes, 480V maximum.
When group installed with the specified line reactor frame D, E, F, G, H, J and K sizes may be used on a supply rating delivering not more than
50,000 RMS Symmetrical amperes, 480V maximum. Refer to Appendix F: “Technical Specifications” – Supply short circuit rating.
Field Wiring Temperature Rating
Use minimum 75°C Copper conductors.
Listed Accessories / Options
Control Module (AC30 Series)
Graphical Key pad (GKP)
Profibus DP-V1
PROFINET IO
Modbus RTU
DeviceNet
CANopen
EtherNet IP
General Purpose I/O (GPIO) x 3
Encoder Option x 1
Earth bracket kit for C2 filtering
Recommended Wire Sizes
North American wire sizes (AWG) are based on NEC/NFPA-70 for ampacities of thermoplastic-insulated (75ºC) copper conductors.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...