AC30 series Variable Speed Drive
PNO Name
Path
Type
Default
Range
Units
WQ
View
Notes MBus
26:27 STO ACTIVE
27:28 FEEDBACK MISSING
28:29 INTERNAL FAN FAIL
29:30 CURRENT SENSOR
30:31 POWER LOSS STOP
1473 AR Trip Mask.01 OVER VOLTAGE
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03473
1474 AR Trip Mask.02 UNDER VOLTAGE
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03475
1475 AR Trip Mask.03 OVER CURRENT
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03477
1476 AR Trip Mask.04 STACK FAULT
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03479
1477 AR Trip Mask.05 STACK OVER CURRENT
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03481
1478 AR Trip Mask.06 CURRENT LIMIT
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03483
1479 AR Trip Mask.07 MOTOR STALL
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03485
1480 AR Trip Mask.08 INVERSE TIME
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03487
1481 AR Trip Mask.09 MOTOR I2T
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03489
1482 AR Trip Mask.10 LOW SPEED I
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03491
1483 AR Trip Mask.11 HEATSINK OVERTEMP
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03493
1484 AR Trip Mask.12 INTERNAL OVERTEMP
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03495
1485 AR Trip Mask.13 MOTOR OVERTEMP
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03497
1486 AR Trip Mask.14 EXTERNAL TRIP
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03499
1487 AR Trip Mask.15 BRAKE SHORT CCT
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03501
1488 AR Trip Mask.16 BRAKE RESISTOR
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03503
1489 AR Trip Mask.17 BRAKE SWITCH
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03505
1490 AR Trip Mask.18 LOCAL CONTROL
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03507
1491 AR Trip Mask.19 COMMS BREAK
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03509
1492 AR Trip Mask.20 LINE CONTACTOR
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03511
1493 AR Trip Mask.21 PHASE FAIL
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03513
1494 AR Trip Mask.22 VDC RIPPLE
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03515
1495 AR Trip Mask.23 BASE MODBUS BREAK
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03517
1496 AR Trip Mask.24 24 V OVERLOAD
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03519
1497 AR Trip Mask.25 PMAC SPEED ERROR
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03521
1498 AR Trip Mask.26 OVERSPEED
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03523
1499 AR Trip Mask.27 STO ACTIVE
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03525
1500 AR Trip Mask.28 FEEDBACK MISSING
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03527
1501 AR Trip Mask.29 INTERNAL FAN FAIL
Same as PNO 1469
BOOL
TRUE
ALWAYS TECHNICIAN
03529
1502 AR Trip Mask.30 CURRENT SENSOR
Setup::Motor Control::Auto Restart
Parameters::Motor Control::Auto Restart
BOOL
TRUE
ALWAYS TECHNICIAN
03531
1503 AR Trip Mask.31 POWER LOSS STOP
Same as PNO 1502
BOOL
TRUE
ALWAYS TECHNICIAN
03533
1505 AR Initial Delay
Same as PNO 1502
TIME
10.000
0.000 to 3600.000
s
ALWAYS OPERATOR
03537
1506 AR Repeat Delay
Same as PNO 1502
TIME
60.000
0.000 to 3600.000
s
ALWAYS OPERATOR
03539
1507 AR Active
Parameters::Motor Control::Auto Restart
BOOL
NEVER
OPERATOR
03541
1508 AR Restart Pending
Parameters::Motor Control::Auto Restart
BOOL
NEVER
OPERATOR
03543
1509 AR Restarts Remaining
Parameters::Motor Control::Auto Restart
USINT
0 to 20
NEVER
OPERATOR
03545
1510 AR Time Remaining
Parameters::Motor Control::Auto Restart
TIME
0.000 to 3600.000
s
NEVER
OPERATOR
03547
1511 Encoder Supply
Setup::Inputs and Outputs::Option
Parameters::Option IO::Encoder
USINT
(enum)
0
0:5 V
1:12 V
2:15 V
3:24 V
STOPPED TECHNICIAN
03549
1512 Encoder Lines
Same as PNO 1511
DINT
2048
1 to 100000
STOPPED TECHNICIAN
03551
1513 Encoder Invert
Same as PNO 1511
BOOL
FALSE
STOPPED TECHNICIAN
03553
1514 Encoder Type
Same as PNO 1511
USINT
(enum)
0
0:QUADRATURE
1:CLOCK/DIRECTION
STOPPED TECHNICIAN
03555
1515 Encoder Single Ended
Same as PNO 1511
BOOL
FALSE
STOPPED TECHNICIAN
03557
1516 Encoder Speed
Monitor::Inputs and Outputs
Parameters::Option IO::Encoder
REAL
x.
Min to Max
RPM
NEVER
OPERATOR
03559
1517 Encoder Count Reset
Same as PNO 1511
BOOL
FALSE
ALWAYS TECHNICIAN 2
03561
1518 Encoder Count
Same as PNO 1516
DINT
-214783648 to 214783647
NEVER
TECHNICIAN
03563
1520 Actual Rotor T Const
Parameters::Motor Control::Tr Adaptation
REAL
x.
1 to 100000
ms
NEVER
ENGINEER
03567
1521 Tr Adaptation Output
Parameters::Motor Control::Tr Adaptation
REAL
x.
1 to 500
%
NEVER
ENGINEER
03569
1526 Energy Saving Lower Lim
Parameters::Motor Control::Fluxing VHz
REAL
0.00
0.00 to 100.00
%
ALWAYS OPERATOR
03579
1527 Max Available Volts
Parameters::Motor Control::Tr Adaptation
REAL
x.
0 to 10000
V
NEVER
ENGINEER
03581
1528 Demanded Terminal Volts
Parameters::Motor Control::Tr Adaptation
REAL
x.
0 to 1000
V
NEVER
ENGINEER
03583
1529 Terminal Volts
Parameters::Motor Control::Tr Adaptation
REAL
x.
0 to 1000
V
NEVER
ENGINEER
03585
1533 Control Type
Setup::Motor Control::Control and Type
Parameters::Control Mode::Control Mode
USINT
(enum)
0
0:SENSORLESS
1:ENCODER FEEDBACK
STOPPED TECHNICIAN 6
03593
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...