Parameter Reference
D-9
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
DC link voltage demand, setpoint for voltage control loop.
AFE VDC Ramp
1709
Parameters::Regen Control::AFE
0.05
0.01 to 100.00
%
ALWAYS
DC link voltage ramp rate.
AFE VDC Feed Forward
1710
Parameters::Regen Control::AFE
0.0000
-1.5000 to 1.5000
ALWAYS
DC link voltage loop feed forward term.
AFE VDC Min Level
1697
Parameters::Regen Control::AFE
400.00
340.00 to 5000.00
ALWAYS
AFE healthy DC link level, for precharge control, if necessary to be set lower than undervoltage trip level.
AFE Correction Angle
1717
Parameters::Regen Control::AFE
0.00
-90.00 to 90.00
ALWAYS
Angle correction offset.
AFE Transf Angle Offset
1731
Parameters::Regen Control::AFE
0.00
0.00 to 360.00
deg
ALWAYS
Angular offset necessary due to (potential) transformer delta/star connections.
AFE Synchronizing
1712
Parameters::Regen Control::AFE
NEVER
TRUE if AFE in synchronizing state.
AFE Synchronized
1713
Parameters::Regen Control::AFE
NEVER
TRUE if AFE has synchronized to mains frequency.
AFE Enable Drive
1714
Parameters::Regen Control::AFE
NEVER
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...