![Parker AC30 series User Manual Download Page 363](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313363.webp)
Parameter Reference
D-103
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Mot Inv Time Warning
0335
Parameters::Motor Control::Motor Load
NEVER
Only available for IM motor
Output information. Becomes TRUE when the overload is 5% of the maximum value before reducing the current
Mot Inv Time Active
0336
Parameters::Motor Control::Motor Load
NEVER
Only available for IM motor
Output information. Becomes TRUE when overload reaches 100% of the overload limit
Mot Inv Time Output %
0337
Parameters::Motor Control::Motor Load
x.x
0.0 to 500.0
%
NEVER
Only available for IM motor
Actual output limit of the inverse time motor protection.
This value is compared to the Stack Inv Time current limit output to provide the internal limit to the current limit module.
Mot I2T TC
0338
Parameters::Motor Control::Motor Load
0.000 to 1000000.000
s
NEVER
Only available for PMAC motor
Time constant of the motor, define in the PMAC Motor Data module
Mot I2T Active
0340
Parameters::Motor Control::Motor Load
NEVER
Only available for PMAC motor
Motor load has reached 105%
Mot I2T Warning
0341
Parameters::Motor Control::Motor Load
NEVER
Only available for PMAC motor
Motor load has reached 95%
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...