Modbus TCP
A-10
AC30 series Variable Speed Inverter
0942
Modbus Trip Enable
Type: BOOL
Default: FALSE
Base Communications Modbus TCP parameter.
Set TRUE to enable the Modbus Trip. The parameter
Modbus Timeout
must be set to a value other than zero
Range
Writable Saved Config
FALSE
TRUE
1241
Open Connections
Type: USINT
Base Communications Modbus TCP parameter.
Indicates the number of open connections to the inverter Modbus TCP server.
Range
Writable Saved Config
0
…
3
0943
Process Active
Type: BOOL
Base Communications Modbus TCP parameter.
Indicates that a Modbus request addressed to this node has been received within the period set by the parameter
Modbus Timeout
, or
if no timeout is specified, this parameter will stay active after the first received Modbus request.
Range
Writable Saved Config
FALSE
TRUE
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...