6-28
Safe Torque Off
AC30 series Variable Speed Inverter
THE FOLLOWING TEST STEPS MUST BE PERFORMED:
Initial Check:
STO test
Comprehensive Check, Activity
Expected reaction and effect
1
Ensure that no harm can come to personnel or equipment if the motor turns.
2
Apply +24V DC to terminals X10/01 and X10/03.
3
Switch on power to the drive.
No error must be present in the drive system.
X10/05 and /06 must be OFF.
4
Configure the drive and associated equipment if necessary so that it can be started
and stopped, and a speed setpoint provided.
No error must be present in the drive system.
X10/05 and /06 must be OFF.
5
Try to start the drive with a non-zero setpoint. This setpoint value will be referred to as
SPT1 for brevity in these tests. Leave this set throughout all tests.
Drive must start and motor must turn at SPT1.
X10/05 and /06 must be OFF.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...