B-1
Sequencing Logic
AC30 series Variable Speed Inverter
Appendix B:
Sequencing Logic
Drive State Machine
DS402
The sequencing of the inverter is based on the DS402 / DriveCOM / IEC 61800-7 standard as used by most industrial fieldbusses. This allows it
to be easily controlled and monitored by a PLC using the standards’ Control Word and Status Word.
SEQUENCING STATE
The sequencing state of the unit is indicated by an enumerated value given by the
0678 Sequencing State
parameter.
Value
DS402 Sequencing State
Description
0
NOT READY TO SWITCH ON
Not ready to switch on. The drive is initialising or being configured.
1
SWITCH ON DISABLED
The Drive will not accept a switch on command
2
READY TO SWITCH ON
The Drive will accept a switch on command.
3
SWITCHED ON
The Drive will accept an Operation Enable (Run or Jog) command.
- Power stage of the Drive is ready to operate.
- Voltage has not yet been applied to the motor terminals.
4
OPERATIONAL ENABLED
Normal operational state of the drive. This state includes Running, Jogging,
Stopping (Disabling Operation) and Shutting Down (Switching Off).
- Voltage applied to the motor terminals.
5
QUICKSTOP ACTIVE
Emergency stop (Fast stop) is active
6
FAULT REACTION ACTIVE
The Drive is processing a trip event
7
FAULTED
The Drive is tripped awaiting trip reset
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...