Parameter Reference
D-17
AC30 series Variable Speed Drive
1470 AR Mode 1:
Auto Restart
Caution: when Auto Restart is selected the motor may run unexpectedly.
In Auto Restart mode, once the AR feature becomes active it monitors all possible trip sources. Once all trip sources are inactive the AR feature
starts the programmed delay. Once the delay timer expires the AR feature attempts to reset the trip and to restart the motor.
The AR feature will not restart the motor if it was not running at the time of the trip, nor will it restart the motor if the run signal has been removed at
any time since the trip, (even if it is subsequently re-applied). When a motor restart will not be attempted the AR feature will act as if it had been
configured for
Trip Reset
only. If a motor restart will be attempted the parameter
1508 AR Restart Pending
is set TRUE.
Each time a restart is attempted the value in
1509 Restarts Remaining
is decremented. Once this value reaches zero, any further trip selected for
auto restart will cause the AR feature to disable itself.
1470 AR Mode 2:
Auto Start
Caution: when Auto Start is selected the motor may run unexpectedly.
In Auto Start mode, once the AR feature becomes active it monitors all possible trip sources. Once all trip sources are inactive the AR feature starts
the programmed delay. Once the delay timer expires the AR feature attempts to reset the trip and to restart the motor.
The AR feature will attempt to start the motor even if it was not running at the time of the trip, as long as the Sequencing Logic parameter
0644
Control Word
is configured to run, (typically bits 0, 1, 2 and 3 all set), see Appendix B: Sequencing Logic.
In this mode the parameter
1508 AR Restart Pending
is set TRUE. Each time a restart is attempted the value in
1509 Restarts Remaining
is
decremented. Once this value reaches zero, any further trip selected for auto restart will cause the AR feature to disable itself.
Recovery from Self Disabled state
The
AR feature will remain in the Self Disabled state indefinitely. It may be re-activated by the trip condition being reset by some other means, (ie.
Manually by pressing the stop key on the GKP, or remotely using trip reset). Alternatively the AR feature may be re-enabled by setting
1469 AR Enable
to FALSE then back to TRUE.
Indication
When the AR feature is activated the parameter
1507 AR Active
is set TRUE.
While a restart is pending the parameter
1508 AR Restart Pending
is set TRUE. In addition the green LED illuminating the run key on the GKP will
flash.
All indicators are reset once the restart, (or trip reset), attempt has been completed or if the AR feature is disabled.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...