D-102
Parameter Reference
AC30 series Variable Speed Drive
Motor Load
Parameters::Motor Control::Motor Load
Motor Protection, function of the motor type.
The
Motor Load
parameters determines the allowed level of motor overload. This can be especially useful when operating with motors smaller than
the drive rating.
For an IM, an IxT protection is used and provides a current reduction if the max overload level is reached.
The max overload level is calculated based on a 150% for 60s.
For a PMAC motor, the motor load is calculated using the rated motor current and the thermal time constant (2 parameters of the PMAC motor
module). The Thermal time constant is used as the constant time of a simple 1
st
order low pass filter.
% Are all related to rated motor current.
Parameter Name
No.
Path
Default
Range
Units
Writable
100% Mot Current
0332
Parameters::Motor Control::Motor Load
x.x
0.0 to 10000.0
NEVER
Motor current in Amps rms corresponding to 100%
Mot Inv Time Overl'd
0333
Parameters::Motor Control::Motor Load
x.
0 to 500
%
NEVER
Only available for IM motor
Overload % of the motor inverse time protection
Mot Inv Time Delay
0334
Parameters::Motor Control::Motor Load
6.000 to 60.000
s
ALWAYS
Only available for IM motor
Overload time of the motor inverse time protection from cold state
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...