Installation
4-30
AC30 series Variable Speed Inverter
APPLICATION 2: RAISE / LOWER TRIM
Application 2:
“Speed Raise/Lower”
IDEAL FOR APPLICATIONS REQUIRING SPEED
CONTROL FROM MULTIPLE LOCATIONS
ANIN 01
(X11/01)
ANIN 02
(X11/02)
RAMP
0486
Acceleration Time
0487
Deceleration Time
Not Used
Not Used
CURRENT LIMIT
V/F SHAPING
CT
VT
V
F
PWM CONTROL
I FDBK
F
V
F
V
0484
Seq Stop Method
DIGIN 01
(X13/02)
DIGIN 02
(X13/03)
DIGIN 03
(X13/04)
DIGIN 04
(X12/01)
DIGIN 05
(X12/02)
DIGIN 06
(X12/03)
DIGIN 07
(X12/02)
RUN
LOWER SPEED
RAISE/LOWER RESET
NOT COAST STOP
NOT QUICKSTOP
TRIP RESET
RAISE SPEED
0422
Vhz Shape
0457
Base Frequency
0447
Fixed Boost
0455
Rated Motor Current
ANOUT 01
(X11/03)
ANOUT 02
(X11/04)
SPEED DEMAND
MOTOR CURRENT
SEQUENCING LOGIC
1901
Ramp Time
1902
Reset Value
1903
Maximum Value
1904
Minimum Value
RAISE/LOWER
MIN /MAX SPEED
1264
Ref Min Speed Clamp
1265
Ref Max Speed Clamp
0504
Stop Ramp Time
0508
Quickstop Ramp Time
FEEDBACKS
RUNNING
NOT
TRIPPED
RELAY 01
(X14/01)
(X14/02)
RELAY 02
(X14/03)
(X14/04)
RELAY 11
(X23/01)
(X23/02)
if AC30V
Requires IO Option
7004-01-00
RELAY 12
(X23/03)
(X23/04)
if AC30V
Requires IO Option
7004-01-00
OR
OR
Raise/Lower Trim Application
This Application mimics the operation of a motorised potentiometer. Digital inputs allow the setpoint to be increased and decreased between
limits. The limits and ramp rate can be set using the keypad.
The Application is sometimes referred to as Motorised Potentiometer.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...