Parameter Reference
D-13
AC30 series Variable Speed Drive
Auto Restart
Setup:: Motor Control::Auto Restart
Parameters::Motor Control::Auto Restart
The Auto Restart feature provides the facility to automatically reset a choice of trip events and restart the drive with a programmed number of
attempts. The number of attempted restarts is monitored. A manual or remote trip reset is required if the drive is not successfully restarted within the
maximum number of restarts. The purpose of this feature is to allow automatic recovery from trip conditions. This is especially useful on remote or
unmonitored sites.
Parameter Name
No.
Path
Default
Range
Units
Writable
AR Enable
1469
Setup::Motor Control::Auto Restart
Parameters::Motor Control::Auto Restart
FALSE
ALWAYS
Enables the auto restart function.
AR Mode
1470
Same as PNO 1469
1
0:TRIP RESET
1:AUTO RESTART
2:AUTO START
ALWAYS
Defines the action that the AR function will take following a trip.
0.
TRIP RESET
Trips will be reset when the trip sources are inactive. The drive will not be restarted.
1.
AUTO RESTART
If it was running the drive will be restarted when the trip sources are inactive and run is active.
2.
AUTO START
The drive will be started when the trip sources are inactive if the run signal is high
Refer to the Functional Description below for more details.
AR Max Restarts
1471
Same as PNO 1469
10
1 to 20
ALWAYS
Defines the maximum number of restart attempts permitted before the AR function disables itself.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...