![Parker AC30 series User Manual Download Page 373](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313373.webp)
Parameter Reference
D-113
AC30 series Variable Speed Drive
PID
Setup::Application::PID
Monitor::Application::PID*
This function allows the AC30V to be used in applications requiring a trim to the reference, depending on feedback from an external measurement
device. Typically this will be used for process control, i.e. pressure or flow.
Parameter Name
No.
Path
Default
Range
Units
Writable
Setpoint
This is connected to an Analog Input as part of the selected macro.
Feedback
This is connected to an Analog Input as part of the selected macro.
Enable
This is connected to a Digital Input as part of the selected macro. It globally resets the PID output and integral term when FALSE.
Enable
must be TRUE for the PID to operate.
Integral Defeat
This may be connected to a Digital Input as part of the selected macro. It resets the p integral term when FALSE.
PID Setpoint Negate
1926
Monitor::Application::Preset Speeds
REAL
-100.0 to 100.0
%
NEVER
Changes the sign of the Setpoint input
PID Feedback Negate
1927
Setup::Application::PID
BOOL
ALWAYS
Changes the sign of the Negate input
PID Proportional Gain
1928
Setup::Application::PID
REAL
ALWAYS
This is the true proportional gain of the PID controller. When set to zero the PID Output is zero.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...