![Parker AC30 series User Manual Download Page 341](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313341.webp)
Parameter Reference
D-81
AC30 series Variable Speed Drive
General Purpose IO
Monitor::Inputs and Outputs
Parameters::Option IO::General Purpose IO
The General Purpose IO parameters configure the use of the four IO Options, (
Error! Bookmark not defined.
). This group of parameters is only
visible when an IO Option is selected.
Parameter Name
No.
Path
Default
Range
Units
Writable
Anin 11 Value
1181
Monitor::Inputs and Outputs
Parameters::Option IO::General Purpose
IO
x.xx
-100.00 to 100.00
%
NEVER
(Terminal X21.2) - The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale.
Anin 12 Value
1182
Same as PNO 1181
x.xx
-100.00 to 100.00
%
NEVER
(Terminal X21.3) - The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale.
Anin 13 Value
1183
Same as PNO 1181
x.xx
-100.00 to 100.00
%
NEVER
(Terminal X21.4) - The input value expressed as a percentage of range, (+/- 100%), following Offset and Scale.
Anin 11 Offset
1461
Setup::Inputs and Outputs::Option
Parameters::Option IO::General Purpose
IO
0.00
Min to Max
%
ALWAYS
The offset is expressed as a percentage of the hardware range. For example an offset of 10% is equivalent to 1V on the input.
The offset is added to the measured value.
Anin 11 Scale
1462
Same as PNO 1461
1.0000
Min to Max
ALWAYS
The scale is a simple multiplication factor. The input voltage is converted to a percentage value.
1461 Anin 11 Offset
is added and the
result is multiplied by Scale. The result is presented in parameter
1181 Anin 11 Value
.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...