![Parker AC30 series User Manual Download Page 483](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313483.webp)
Parameter Reference
D-223
AC30 series Variable Speed Drive
PNO Name
Path
Type
Default
Range
Units
WQ
View
Notes MBus
3:DISABLED
4:LISTENING
5:PRE_MASTER
6:MASTER
7:PASSIVE
8:UNCALIBRATED
9:SLAVE
1690 AFE Close Ext PCR
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS OPERATOR
03907
1691 AFE Ext PCR Closed
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS OPERATOR
03909
1692 AFE PF Angle Demand
Parameters::Regen Control::AFE
REAL
0.00
-90.00 to 90.00
deg
ALWAYS OPERATOR
03911
1693 AFE Current Control
Setup::Regen Control
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS OPERATOR
03913
1694 AFE PLL Kp
Parameters::Regen Control::AFE
REAL
5.48
0.00 to 30.00
ALWAYS OPERATOR
03915
1695 AFE PLL Ti
Parameters::Regen Control::AFE
REAL
0.0318
0.0000 to 3.0000
ALWAYS OPERATOR
03917
1696 Synth Encoder Lines
Same as PNO 1678
DINT
2048
1 to 15000000
ALWAYS TECHNICIAN
03919
1697 AFE VDC Min Level
Parameters::Regen Control::AFE
REAL
400.00
340.00 to 5000.00
ALWAYS OPERATOR
03921
1698 Synth Encoder Speed
Same as PNO 1678
REAL
0
0 to 15000000
RPM
ALWAYS TECHNICIAN
03923
1699 PTP Clock
Same as PNO 1687
DT
1970/01/01 to 2106/02/07
NEVER
OPERATOR
03925
1701 Switchover Enable
Parameters::Motor Control::MRAS
BOOL
FALSE
ALWAYS ENGINEER
03929
1702 Synth Encoder Invert
Same as PNO 1678
BOOL
FALSE
ALWAYS TECHNICIAN
03931
1703 AFE Sync Frequency
Monitor::Regen Control
Parameters::Regen Control::AFE
REAL
x.xx
Min to Max
Hz
NEVER
OPERATOR
3
03933
1704 AFE Id Demand
Same as PNO 1693
REAL
0.10
-1.50 to 1.50
ALWAYS OPERATOR
03935
1705 AFE Iq Demand
Same as PNO 1693
REAL
0.00
-1.50 to 1.50
ALWAYS OPERATOR
03937
1706 AFE Max Current
Parameters::Regen Control::AFE
REAL
1.50
0.00 to 1.50
ALWAYS OPERATOR
03939
1707 AFE VDC Kp
Parameters::Regen Control::AFE
REAL
8.27
0.00 to 300.00
ALWAYS OPERATOR
03941
1708 AFE VDC Ti
Parameters::Regen Control::AFE
REAL
0.03
0.00 to 3.00
ALWAYS OPERATOR
03943
1709 AFE VDC Ramp
Parameters::Regen Control::AFE
REAL
0.05
0.01 to 100.00
%
ALWAYS OPERATOR
03945
1710 AFE VDC Feed Forward
Parameters::Regen Control::AFE
REAL
0.0000
-1.5000 to 1.5000
ALWAYS OPERATOR
03947
1711 AFE VDC Demand
Same as PNO 1693
REAL
720
340 to 820
V
ALWAYS OPERATOR
03949
1712 AFE Synchronizing
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3
03951
1713 AFE Synchronized
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3
03953
1714 AFE Enable Drive
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3
03955
1715 AFE Phase Loss
Parameters::Regen Control::AFE
BOOL
NEVER
OPERATOR
3
03957
1716 AFE Brake Mode
Parameters::Regen Control::AFE
BOOL
FALSE
ALWAYS OPERATOR
03959
1717 AFE Correction Angle
Parameters::Regen Control::AFE
REAL
0.00
-90.00 to 90.00
ALWAYS OPERATOR
03961
1718 AFE Sync Angle
Parameters::Regen Control::AFE
REAL
x.xx
Min to Max
deg
NEVER
OPERATOR
3
03963
1721 AFE Status
Same as PNO 1703
USINT
(enum)
0:INACTIVE
1:SYNCHRONIZING
2:SYCHRONIZED
3:SUPPLY FREQ HIGH
4:SUPPLY FREQ LOW
5:SYNC FAILED
NEVER
OPERATOR
3
03969
1722 SB Digital Input 2
Monitor::Inputs and Outputs
Parameters::System Board::System Board IO
BOOL
NEVER
OPERATOR
03971
1723 SB Digital Input 3
Same as PNO 1722
BOOL
NEVER
OPERATOR
03973
1725 Peer to Peer Enable
Setup::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
BOOL
FALSE
ALWAYS TECHNICIAN
03977
1726 Destination IP Address
Same as PNO 1725
DWORD
(IP addr)
255.255.255.255
ALWAYS ENGINEER
03979
1727 Destination Port
Same as PNO 1725
UINT
1250
1 to 65535
ALWAYS ENGINEER
03981
1728 Local Port
Same as PNO 1725
UINT
1250
1 to 65535
ALWAYS ENGINEER
03983
1729 Peer to Peer State
Monitor::Communications::Peer to Peer
Parameters::Base Comms::Peer to Peer
USINT
(enum)
0:DISABLED
1:ACTIVE
2:ERROR
NEVER
OPERATOR
03985
1730 AFE Inductance
Setup::Regen Control
Parameters::Regen Control::AFE
REAL
0.00
0.00 to 1000.00
mH
ALWAYS OPERATOR
03987
1731 AFE Transf Angle Offset
Parameters::Regen Control::AFE
REAL
0.00
0.00 to 360.00
deg
ALWAYS OPERATOR
03989
1732 Motor Start Count
Parameters::Device Manager::Runtime Statistics
UDINT
0 to Max
NEVER
TECHNICIAN 1
03991
1733 Time Since Power-On
Parameters::Device Manager::Runtime Statistics
TIME
0.000 to Max
s
NEVER
TECHNICIAN
03993
1734 AR Trip Mask B
Parameters::Motor Control::Auto Restart
DWORD
00000000
ALWAYS TECHNICIAN
03995
1735 AR Trip Mask 2 B
Parameters::Motor Control::Auto Restart
DWORD
00000000
ALWAYS TECHNICIAN
03997
1736 AR Initial Delay B
Parameters::Motor Control::Auto Restart
TIME
60.000
0.000 to 3600.000
s
ALWAYS OPERATOR
03999
1737 AR Repeat Delay B
Parameters::Motor Control::Auto Restart
TIME
120.000
0.000 to 3600.000
s
ALWAYS OPERATOR
04001
1738 Enable Auto Save
Parameters::Device Manager::Setup Wizard
BOOL
TRUE
ALWAYS ENGINEER
04003
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...