Safe Torque Off
6-9
AC30 series Variable Speed Inverter
STO Technical Specification
INPUTS SPECIFICATION
STO A Input and STO B Input comply with IEC61131-2. Note: inputs do not have hysteresis.
Recommended input voltage for low level:
0V to +5V
Recommended input voltage for high level:
+21.6V to +26.4V
Typical input threshold voltage:
+10.5V
Indeterminate input range:
+5V to +15V. Function is undefined.
Absolute maximum input voltage:
-30V to +30V
Typical input current @ 24V
9mA
Fault detection time
4
:
2.3sec typical;
< 1.6sec will not generate a fault
> 3.0sec will generate a fault.
Response time
5
> 2ms
6ms typical
< 10ms
Conditions in which the STO inputs are operative:
All, i.e. STO cannot be disabled in any condition
4
A fault is defined in this context as STO A Input and STO B Input being sensed in opposite logic states.
5
Response time is the time from the first STO input becoming active (voltage level is low) until torque production has ceased
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...