Parameter Reference
D-21
AC30 series Variable Speed Drive
Functional Description
You MUST carry out an Autotune if you intend to use the drive in vector control mode. If you are using it in
Volts/Hz control an Autotune is not necessary.
Autotune can only be initiated from the “stopped” condition. When the test is complete, the stack is disabled and Autotune Enable is set to FALSE.
Note
Refer to the Chapter 9: Setup Wizard for details on how to perform an Autotune.
Standard Autotune
If an induction motor is fitted, the autotune will identify parameters as follows.
Parameter
Description
Note
MAG CURRENT
Magnetising current
Not measured by Stationary Autotune
STATOR RES
Per phase stator resistance
LEAKAGE INDUC
Per phase stator leakage inductance
MUTUAL INDUC
Per phase mutual inductance
ROTOR TIME CONST
Rotor time constant
This will be identified while the motor is spinning, while measuring the
magnestising current. If stationary autotune is selected, it will be
identified from magnetising current and motor nameplate rpm
The Rotating autotune sequence rotates the motor up to the user-programmed MAX SPEED (
Scale Setpoint
function) in order to
identify these parameters. (A rotating autotune is required if the motor is to be operated above base speed).
The Stationary autotune sequence does not rotate the motor and requires the correct value of MAG CURRENT to be entered.
(Stationey Autotune should only be considered if roatating autotune is not possible to execute).
If a permanent magnet motor is fitted, the autotune will identify parameters as follows.
Parameter
Description
Note
STATOR RES
Phase to phase stator resistance
LEAKAGE INDUC
Phase to phase stator leakage inductance
KE CONSTANT
Back-emf constant
This will be identified while the motor is spinning. If stationary autotune
is selected, it will be identified from motor nameplate parameters
The Stationary autotune sequence does not rotate the motor and requires the correct permanant magnet nameplate value to be
entered.
The Rotating autotune sequence rotates the motor up to the half of the rated motor speed in order to identify these parameters.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...