![Parker AC30 series User Manual Download Page 184](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313184.webp)
12-19
Ethernet
AC30 series Variable Speed Inverters
PTP Profile
Each PTP device has a set of attributes as define by IEEE1588-2008. On the inverter the default attributes values are set as follows. Note that
some may be modified by a parameter.
Attribute
Description
Inverter default value
Modified by parameter
domainNumber
A domain consists of one or more PTP devices
communicating with each other. Devices on the
same domain will have the same domain number.
0
-
slaveOnly
When
slaveOnly
is TRUE the PTP device may only
be a slave and not become a master clock.
FALSE
1684 PTP Clock Type
logAnnounceInterval
A port in the MASTER state will periodically transmit
an Announce message.
Announce messages will be transmitted such that the
logarithm to the base 2 of the mean value of the
interval in seconds between message transmissions
is the value of the
logAnnounceInterval
.
1
(2 seconds)
-
logSyncInterval
A port in the MASTER state will periodically transmit
a Sync message.
Sync messages will be transmitted such that the
logarithm to the base 2 of the mean value of the
interval in seconds between message transmissions
is the value of the
logSyncInterval
.
-1
(0.5 seconds)
1681 PTP Log Sync Interval
logMinDelayReqInterval
The
logMinDelayReqInterval
will specify the
minimum permitted mean time interval between
successive Delay_Req messages.
This value is determined and advertised by a master
clock based on the ability of the master clock to
process the Delay_Req message traffic.
0
-
announceReceiptTimeout
The value of
announceReceiptTimeout
will specify
the number of announceInterval that has to pass
without receipt of an Announce message
3
-
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...