![Parker AC30 series User Manual Download Page 351](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313351.webp)
Parameter Reference
D-91
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Anout 01 ABS
1441
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO
Configure
FALSE
ALWAYS
When ABS is set TRUE, the absolute value of the result of combining
0042 Anout 01 Value
,
0686 Anout 01 Scale
and
1108 Anout 01 Offset
is used to drive the output electronics.
Anout 02 Type
0004
Same as PNO 1
1
1:0..10 V
2:0..20 mA
3:4..20 mA
ALWAYS
Analog output 1 is associated with terminal X11.4
The signal processing electronics for analog output 2 supports the three output ranges
Anout 02 Scale
1460
Same as PNO 1441
1.0000
Min to Max
ALWAYS
The scale is a simple multiplication factor applied to
0043 Anout 02 Value
.
Anout 02 Offset
1467
Same as PNO 1441
0.00
Min to Max
%
ALWAYS
The offset is expressed as a percentage of the hardware range selected by
0004 Anout 02 Type
. For example, with the 4..20mA
range an offset of 10% is equivalent to 1.6mA on the output.
The demand value
0043 Anout 02 Value
is multiplied by
1460 Anout 02 Scale
then added to the Offset. The resultant value is then
limited to 0..100%.
Anout 02 ABS
1468
Same as PNO 1441
FALSE
ALWAYS
When ABS is set TRUE, the absolute value of the result of combining
0043 Anout 02 Value
,
1460 Anout 02 Scale
and
1467 Anout 02 Offset
is used to drive the output electronics.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...