![Parker AC30 series User Manual Download Page 350](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313350.webp)
D-90
Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Anin 02 Offset
0959
Same as PNO 957
0.00
Min to Max
%
ALWAYS
The offset is expressed as a percentage of the hardware range selected by
0002 Anin 02 Type
. For example, with the -10..10V range
an offset of 10% is equivalent to 1v on the input.
The offset is added to the measured value.
Anin 02 Scale
0960
Same as PNO 957
1.0000
Min to Max
ALWAYS
The scale is a simple multiplication factor. The input voltage is converted to a percentage value.
0959 Anin 02 Offset
is added and the
result is multiplied by
0960 Anin 02 Scale
. The result is presented in parameter
0041 Anin 02 Value
.
Anout 01 Type
0003
Same as PNO 1
0
Same as PNO 2
ALWAYS
Analog output 1 is associated with terminal X11.3
The signal processing electronics for analog output 1 supports two output ranges:
0.
-10..10V
1.
0..10V
Anout 01 Scale
0686
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO
Configure
1.0000
Min to Max
ALWAYS
The scale is a simple multiplication factor applied to
0042 Anout 01 Value
.
Anout 01 Offset
1108
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO
Configure
0.00
Min to Max
%
ALWAYS
The offset is expressed as a percentage of the hardware range selected by
0003 Anout 01 Type
. For example, with the -10..10V
range an offset of 10% is equivalent to 1v on the output.
The demand value
0042 Anout 01 Value
is multiplied by
0686 Anout 01 Scale
then added to the Offset. The resultant value is then
limited to -100 to 100%, (for the -10..10V type) or 0..100%, (for the 0..10V range).
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...