![Parker AC30 series User Manual Download Page 82](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313082.webp)
6-4
Safe Torque Off
AC30 series Variable Speed Inverter
Most but not all single component failures will be detected. Diagnostic Coverage (DC) is required to be at least 60% (i.e. the
minimum required for ‘low’ diagnostic coverage).
Detected component failures will result in the STO function being applied without intervention from the user.
The risk associated with the loss of STO safety function caused by multiple failures must be understood and accepted by the
user.
The user must undertake a risk analysis and specify suitable components that, when connected together, meet the risk
assessment requirements.
Mean Time To Failure (dangerous) (MTTFd) of each STO channel must be ≥ 30 years.
Common Cause Failure (CCF) score must be ≥ 65 according to Annex F of the standard.
Performance Level (PL) e:
Average probability of dangerous failure per hour (PFH) must be ≤ 10
-7
EN61800-5-2:2007 AND EN61508
(Adjustable speed electrical power drive systems) and
(Functional safety of electrical/electronic/programmable electronic safety-related systems)
STO aligns to the following aspects of this standard:
Safety Integrity Level (SIL) 3
Probability of dangerous random hardware failures per hour (PFH) must be ≤ 10
-7
Subsystems type A according to EN61508-2:2001 para 7.4.3.1.2
Hardware Fault Tolerance (HFT) = 1
Safe Failure Fraction (SFF) must be ≥ 90%
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...