![Parker AC30 series User Manual Download Page 396](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313396.webp)
D-136
Parameter Reference
AC30 series Variable Speed Drive
Raise Lower
Setup::Application::Raise Lower
Monitor::Application::Raise Lower*
Appears when the
Raise/Lower
macro is selected.
The
Raise/Lower
function acts as an internal motorised potentiometer (MOP) used as a reference source.
Parameter Name
No.
Path
Default
Range
Units
Writable
RL Ramp Time
1901
Setup::Application::Raise Lower
10.0
0.0 to 600.0
s
ALWAYS
Rate of change of the
Output
. Defined as the time to change from 0.00% to 100.00% . Note that the raise and lower rates are always
the same.
L Reset Value
1902
Setup::Application::Raise Lower
0.0
-500.0 to 500.0
%
ALWAYS
The value Output is set to when the Reset Input is TRUE.
RL Maximum Value
1903
Setup::Application::Raise Lower
100.0
-500.0 to 500.0
%
ALWAYS
The maximum value to which
Output
will ramp up to.
RL Minimum Value
1904
Setup::Application::Raise Lower
-100.0
-500.0 to 500.0
%
ALWAYS
The minimum value to which
Output
will ramp down to.
Reset Input
This is connected to a Digital Input as part of the selected Macro. When TRUE forces
Output
to track
Reset Value
.
Raise Input
This is connected to a Digital Input as part of the selected Macro. When TRUE causes
Output
to ramp up.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...