![Parker AC30 series User Manual Download Page 409](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313409.webp)
Parameter Reference
D-149
AC30 series Variable Speed Drive
Sequencing
Parameters::Motor Control::Sequencing
These parameters allow the user of the AC30V to monitor the status and affect the behaviour of the DS402 drive state machine as described in
detail in Appendix B “Sequencing Logic”.
Parameter Name
No.
Path
Default
Range
Units
Writable
Local
0591
Parameters::Motor Control::Sequencing
FALSE
ALWAYS
Local (GKP) of Control and Reference.
Local Power Up Mode
1565
Parameters::Motor Control::Sequencing
0
0:AS WHEN POWERED DOWN
1:LOCAL
2:REMOTE
ALWAYS
The initial value of
0591
Local
can be selected by the User using this enumerated parameter.
0: AS WHEN POWERED DOWN
the state when the Drive was powered down (default)
1: LOCAL
always powers up with
0591
Local
set to TRUE
2: REMOTE
always powers up with
0591
Local
set to FALSE
Local Reference
0592
Parameters::Motor Control::Sequencing
0.00
0.00 to 100.00
%
ALWAYS
Local Reference from GKP.
App Control Word
0610
Parameters::Motor Control::Sequencing
0000
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
ALWAYS
Control Word from Application (Terminals).
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...