![Parker AC30 series User Manual Download Page 18](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313018.webp)
3-2
Product Overview
AC30 series Variable Speed Inverter
Control Features
The inverter is fully featured when controlled using the optional Keypad (or a suitable pc programming tool).
The ‘General’ control features below are not user-selectable when the unit is controlled using the analog and digital inputs and outputs.
General
Output Frequency
Limited to Switching Frequency divided by 8, with a maximum of 590Hz.
e.g.
for 4kHz switching frequency it is 4000/8 = 500Hz,
for 16kHz switching frequency it is 590Hz. Refer to Parker SSD for higher output frequency.
Derating of output current may apply, refer to Appendix F Technical Specifications.
Switching Frequency
Minimum 2kHz.
Maximum 8kHz – 16kHz dependent on frame size and motor type (Induction or PMAC)
Voltage Boost for V/F
control
0-25%
Motor Control Modes
Induction motor: VHz control, Sensorless Vector Control, or Closed Loop Vector Control (with
encoder if fitted). Sensorless and Closed Loop Vector require autotune.
PMAC motor: Sensorless Vector Control
Skip Frequencies
Skip frequencies with adjustable skip band width
Preset Speeds
User selectable preset speeds
Stopping Modes
Ramp, Coast, DC Injection, Quickstop
S Ramp and Linear Ramp Symmetric or asymmetric ramp up and down rates
Raise/Lower
Programmable MOP function
Jog
Programmable jog speed
Diagnostics
Full diagnostic and monitoring facilities
Protection
Trip Conditions
Output short line to line, and line to earth
Overcurrent > 220% HD current
Stall
Heatsink overtemperature
Motor Thermistor overtemperature (using optional GPIO)
Overvoltage and undervoltage
Current Limit
Adjustable 110% (Normal Duty) or 150% (Heavy Duty)
180% shock load limit (Heavy Duty)
Inverse Time
Dual Rating
Normal duty (110% overload for 60s)
Heavy duty (150% overload for 60s)
Inputs/
Outputs
Analog Inputs
2 configurable inputs; voltage or current
Analog Outputs
2 configurable outputs; voltage or current
Digital Inputs
3 configurable 24V dc inputs
Digital I/O
4 configurable 24V dc open collector outputs/digital inputs
Relay Outputs
2 configurable relay output
Table 3-1 Control Features
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...