![Parker AC30 series User Manual Download Page 187](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313187.webp)
Ethernet
12-22
AC30 series Variable Speed Inverters
Parameter Name
No.
Path
Default
Range
Units
Writable
PTP Priority2
1686
Setup::Communications::PTP
Parameters::Base Comms::PTP
128
0 to
255
ALWAYS
PTP parameter.
Sets the Priority 2 used as part of the process in determining which PTP device becomes the master clock. See description in
section
Advanced Configuration
for more details.
PTP Lock Threshold
1685
Setup::Communications::PTP
Parameters::Base Comms::PTP
0.5 us
0.1 us to
100 us
us
ALWAYS
PTP parameter.
Sets the Lock Threshold when the inverter is a slave clock. When the average offset between the slave clock and the master clock
falls below the Lock Threshold then the slave clock is deemed to be synchronised as indicated by the parameter 1688 PTP Locked.
Note that it will take longer for a slave clock to be deemed synchronised when a smaller threshold is set.
PTP State
1689
Monitor::Communications::PTP
Parameters::Base Comms::PTP
NONE
0:NONE
1:INITIALISNG
2:FAULTY
3:DISABLED
4:LISTENING
5:PRE-MASTER
6:MASTER
7:PASSIVE
8:UNCALIBRATED
9:SLAVE
NEVER
PTP parameter.
A diagnostic parameter indicating the state of the internal PTP state machine.
Enumerated values:
0: NONE
- the PTP module is disabled or the Ethernet cables are removed
1: INITIALISNG
- the PTP is initialising the data sets and communications
2: FAULTY
- the PTP module failed to initialise
3: DISABLED
- the PTP will not send any messages and will accept only PTP management messages
4: LISTENING
- the PTP is listening for Announce messages from a master or waiting to timeout on received announce
messages.
5: PRE-MASTER
- the PTP behaves as though it were in the MASTER state but will not send any messages except for
peer delay, signalling or management messages.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...