Trips & Fault Finding
10-9
AC30 series Variable Speed Inverter
CODE
ERROR
Possible Reason for Error
1302
HTTP server fault
Record the error message and contact Technical Support
1303
DCT server fault
Record the error message and contact Technical Support
1303
DCT server fault
Record the error message and contact Technical Support
1311
Ethernet PHY
Record the error message and contact Technical Support
1312
Precision Time
Protocol
Record the error message and contact Technical Support
1401
1402
Control Module test
Control module self-test error
1403
1404
Power stack test
VCM not secured to power stack
Power stack self-test error
1501
1502
1503
IO Option identity
IO Option processor
Unknown IO Option
Ensure the IO option is correctly fitted
Update the firmware in the inverter.
Replace the IO option
1504
IO Option watchdog
The IO Option has become disconnected
Option reset problem. Upgrade drive firmware to 1.11 or greater to improve the option reset control.
1601
Stack internal fault
Return the power stack to Parker Hannifin repair center.
1602
Incompatible stack
Return the power stack to Parker Hannifin repair center.
1801
Heatsink thermsistor
unplugged
Return the power stack to Parker Hannifin repair center.
1901
System Board Data
The identifying data on the system board is corrupt
1902
System Board Type
The system board type is not recognized by this version of drive firmware. Update the firmware to the latest
version.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...