Sequencing Logic
B-6
AC30 series Variable Speed Inverter
Example Comms Control Words (hexadecimal):
CC77 STOP (Normal) or go to SWITCHED ON state
CC7F RUN
CC7B QUICKSTOP
CC7D COAST STOP
CCF0 FAULT RESET
STATUS WORD
The Status Word provides the detailed status of the sequencer. Regardless of the source of the Control Word, this is always available as
0661
Status Word
.
Bit
Name
Description
0
Ready To Switch On
Drive initialised and not in Configuration mode
1
Switched On
Drive in SWITCHED ON or OPERATION ENABLED state
2
Operation Enabled
Running (or stopping)
3
Faulted
Unacknowledged fault present
4
Voltage Enabled
Line supply present
5
Quickstop Inactive
= 0 when reacting to a Quickstop request
6
Switch On Disabled
Drive in SWITCH ON DISABLED state
7
unused
8
unused
9
Control From Comms
Using
0627 Comms Control Word
as the Control Word source
10
unused
11
unused
12
Jog Operation
Using Jog Reference or will use Jog Reference when Operation Enabled
13
Reverse Operation
Running backwards or will run backward when Operation Enabled
14
Reference From Comms Using
0681 Comms Reference
as the Reference source
15
Stopping
Operation Enable command removed or Quickstop active
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...