Trips & Fault Finding
10-3
AC30 series Variable Speed Inverter
ID
Trip Name
Possible Reason for Trip
Criteria for Warning
7
MOTOR STALL
The motor has stalled (not rotating) Drive in current limit >200 seconds:
Motor loading too great
FIXED BOOST level set too high
The stall condition has been
detected for more than one tenth
of the configured Stall Time.
8
INVERSE TIME
A prolonged overload condition, exceeding the Inverse Time allowance, has caused
the trip:
Remove the overload condition
An overload condition has
exceeded one half of the Inverse
Time allowance.
9
MOTOR I2T
Only for PMAC Motor: A prolonged load condition, exceeding the motor rated current,
has caused the trip. The estimated motor load has reached a value of 105%
An overload condition has
exceeded one half of the motor
Inverse Time allowance.
10
LOW SPEED I
The motor is drawing too much current (>100%) at zero output frequency:
FIXED BOOST level set too high
Not applicable.
11
HEATSINK
OVERTEMP
Drive heatsink temperature too high
The ambient air temperature is too high
Poor ventilation or spacing between drives
Check heatsink fan is rotating
The drive heatsink has exceeded
the warning temperature level
(which is approx. 10
C below
the trip temperature).
12
INTERNAL
OVERTEMP
Processor temperature or ambient temperature within the power stage too high
The ambient temperature in the drive is too high
The drive processor temperature
has exceeded the warning
temperature level (which is
approx. 10
C below the trip
temperature).
13
MOTOR
OVERTEMP
The motor temperature is too high, (required IO Option card)
Excessive load
Motor voltage rating incorrect
FIXED BOOST level set too high
Prolonged operation of the motor at low speed without forced cooling
Break in motor thermistor connection
The motor has been over
temperature for 7.5 seconds.
14
EXTERNAL TRIP
The external (application) trip input is high:
Refer to the application description to identify the source of the signal
Not applicable.
15
BRAKE SHORT
CCT
External dynamic brake resistor has been overloaded:
The external dynamic brake has developed a short circuit.
Wiring fault
Not applicable.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...