Safe Torque Off
6-31
AC30 series Variable Speed Inverter
User Output Check:
STO test
Comprehensive Check, Activity
Expected reaction and effect
19
Remove connections to X10/01 and X10/03 within 1 second of each other.
X10/05 and /06 must be ON.
20
Try to restart the drive.
Wait for at least 10 seconds with the run command active, then remove it.
Drive must not start while run command is given.
Drive must report STO trip immediately.
X10/05 and /06 must remain ON.
21
Reconnect X10/01 and X10/03 to 24V.
X10/05 and /06 must turn OFF immediately.
22
Try to restart the drive at SPT1.
STO trip must clear.
The drive must restart at SPT1.
23
Stop the drive.
Test is complete.
Drive must stop.
The tests specified above are the minimum set; further test steps may be required depending on the application, for example a controlled stop should be
verified in a SS1 application.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...