![Parker AC30 series User Manual Download Page 195](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313195.webp)
Fire Mode
13-5
AC30 series Variable Speed Drive
ID
Trip Name
Disabled in Partial mode
Disabled in Full mode
Drive Protection
23
BASE MODBUS BREAK
24
24V OVERLOAD
25
PMAC SPEED ERROR
26
OVERSPEED
27
SAFE TORQUE OFF
Note 1. The Under Voltage trip is enabled when Fire Mode is active, but the trip level is reduced by 50%.
If a trip source becomes active when the associated trip is disabled the drive will continue to run. This is also the normal behavior of the drive, (when
Fire Mode is not active). If the associated trip is designed for drive protection, this will be recorded in non-volatile memory. The recorded values are
available to view in the Trips History parameter block, (refer to Appendix D).
When Fire Mode is activated and a trip source becomes active and the associated trip is enabled, the drive will trip, causing the motor to stop. This
is similar to the normal behavior of the drive, (when Fire Mode is not active). However, when Fire Mode is active the drive firmware continues to
monitor the trip source, once the trip source has become inactive the drive automatically resets the trip condition and restarts the drive.
The Fly catching feature can be used to allow the drive to smoothly resume control of a moving load on restart.
Motor Control Modes
The operation of Fire Mode is independent of the motor type motor and the control mode, (Open Loop or Sensorless Vector control).
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...