Parameter Reference
D-19
AC30 series Variable Speed Drive
which the autotune was carried out, this will not be allowed. If in doubt, the autotune speed is recorded in the parameter Max Spd When Autotuned,
described below.
Parameter Name
No.
Path
Default
Range
Units
Writable
Autotune Enable
0255
Setup::Motor Control::Autotune
Parameters::Motor Control::Autotune
FALSE
STOPPED
Puts the autotune feature into a state where it will carry out the autotune when the drive is started.
Autotune Mode
0256
Same as PNO 255
1
0:STATIONARY
1:ROTATING
STOPPED
Selects whether the autotune is carried out on a rotating motor, or whether it just calculates from nameplate data (not the preferred
method). It may be necessary to carry out a stationary autotune if the motor is not free to rotate, for example if it is already connected
to a machine. Leakage inductance (to tune the current loop) and stator resistance may be measured when the motor is stationary, but
other parameters can only be inferred from nameplate data. Use the rotating autotune where possible.
Nameplate Mag Current
1550
Setup::Motor Control::Autotune
Parameters::Motor Control::Autotune
1.00
0.01 to 1000.00
A
STOPPED
This parameter will only become visible if Autotune Mode = STATIONARY is selected.
If you select stationary autotune, you must enter the motor magnetising current into this parameter before proceeding with the
stationary autotune. If this is not known, it can be approximated from the motor rated current and the power factor, as motor current
times √(1 – PF^2).
The value of mag current entered here will be copied into the magnetising current parameter in the Induction Motor Data menu. If a
rotating autotune is run at a later date, it will be replaced with the more accurate value, and this parameter will be irrelevant.
Autotune Test Disable
0257
Same as PNO 255
0000
0:Stator Resistance
1:Leakage Inductance
2:Magnetising Current
3:Rotor Time Constant
4:Encoder Direction
STOPPED
This is only valid for induction motor autotune
Allows selected tests to be disabled (default all tests are carried out).
Each test can be individually disabled by setting to TRUE.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...