Technical Specifications
F-20
AC30 series Variable Speed Drive
ANALOG INPUTS/OUTPUTS
AIN1 (X11/01), AIN2 (X11/02), AOUT1 (X11/03), AOUT2 (X11/04)
Conforming to EN61131-2
Inputs
Output
Range
AIN1:
Range selected by parameter 0001 from:
0 to 10V, -10V to +10V, 0 to 20mA, 4 to 20mA
AIN2:
Range selected by parameter 0002 from:
0 to 10V, -10V to +10V
Absolute maximum input current 25mA in current mode
(AIN1 only)
Absolute maximum input voltage ±24V dc in voltage mode
AOUT1:
Range selected by parameter 0003 from:
0 to 10V, -10V to +10V
AOUT2:
Range selected by parameter 0004 from:
0 to 10V, 0 to 20mA, 4 to 20mA
Maximum rated output current in voltage mode
10mA, with short circuit protection
Impedance
Input impedance:
Voltage range = 22k
Current range = 120R
Load impedance :
Voltage range ≥ 1kΩ
Current range ≤ 600Ω
Resolution
12 bits (1 in 4096) over full range
11 bits (1 in 2048)
Accuracy
Better than ±1%
Better than ±1%
Sample / Update Rate
1ms
1ms
REFERENCE OUTPUTS
+10VREF (X11/05), -10VREF (X11/06)
Output Voltage
+10V and -10V
Accuracy
Better than ±0.5%
Output Current
<10mA
Overload / Short
Circuit Protection
Indefinite
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...