![Parker AC30 series User Manual Download Page 414](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313414.webp)
D-154
Parameter Reference
AC30 series Variable Speed Drive
Skip Frequencies
Setup::Application::Skip Frequencies
Function availability depends on macro selected.
This function is used to prevent the Drive operating at frequencies that cause mechanical resonance in the load.
Parameter Name
No.
Path
Default
Range
Units
Writable
Skip Band 1
1908
Setup::Application::Skip Frequencies
0.0
0.0 to 1000.0
Hz
ALWAYS
The width of skip band 1 in Hz.
Skip Frequency 1
1909
Setup::Application::Skip Frequencies
0.0
0.0 to 1000.0
Hz
ALWAYS
The centre frequency of skip band 1 in Hz.
Skip Band 2
1910
Setup::Application::Skip Frequencies
0.0
0.0 to 1000.0
Hz
ALWAYS
The width of skip band 2 in Hz.
Skip Frequency 2
1911
Setup::Application::Skip Frequencies
0.0
0.0 to 1000.0
Hz
ALWAYS
The centre frequency of skip band 2 in Hz.
Skip Band 3
1912
Setup::Application::Skip Frequencies
0.0
0.0 to 1000.0
Hz
ALWAYS
The width of skip band 3 in Hz.
Skip Frequency 3
1913
Setup::Application::Skip Frequencies
0.0
0.0 to 1000.0
Hz
ALWAYS
The centre frequency of skip band 3 in Hz.
Skip Band 4
1914
Setup::Application::Skip Frequencies
0.0
0.0 to 1000.0
Hz
ALWAYS
The width of skip band 4 in Hz.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...