Trips History
Parameters::Trips::Trips History
Parameter Name
No.
Path
Default
Range
Units
Writable
Recent Trips
0895
Parameters::Trips::Trips History
NEVER
The Recent Trips array is a record of the last 10 faults that caused the drive to disable the stack. Each entry has the same format as
the First Trip parameter, (see
Trips Status
). The most recent fault is the first entry in the array, (Recent Trips[0]).
Recent Trip Times
1442
Parameters::Trips::Trips History
NEVER
The time of each of the recent trips. The time saved is a snapshot of the Control Board Up Time, see
Runtime Statistics
.
Warranty Trips
0968
Parameters::Trips::Trips History
NEVER
The Warranty Trips array is a record of the last 3 drive protection trips that were ignored due to the trip being disabled. This will usually
be because Fire Mode (see Chapter 13) is enabled. Each entry has the same format as the First Trip parameter, (see
Trips Status
).
The most recent fault is the first entry in the array, (Warranty Trips[0]).
Warranty Trip Time
0972
Parameters::Trips::Trips History
NEVER
The time of each of the Warranty Trips. The time saved is a shapshot of the HV SMPS Up Time, see
Runtime Statistics
.
Warranty Trips Record
1408
Parameters::Trips::Trips History
0:01 OVER VOLTAGE
2:03 OVER CURRENT
3:04 STACK FAULT
4:05 STACK OVER CURRENT
7:08 INVERSE TIME
10:11 HEATSINK OVERTEMP
11:12 INTERNAL OVERTEMP
14:15 BRAKE SHORT CCT
16:17 BRAKE SWITCH
21:22 VDC RIPPLE
NEVER
Records all drive protection trip event that have been ignored due to the trip being disabled. This will usually be because Fire Mode is
enabled. Each entry has the same format as the Active 1
– 32 parameter, (see
Trips Status
).
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...