D-172
Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Short Overload Level
0346
Parameters::Motor Control::Stack Inv
Time
x.
0 to 200
%
NEVER
Overload value in % of the stack amps for short overload condition(*)
Short Overload Time
0347
Parameters::Motor Control::Stack Inv
Time
0.000 to 10000.000
s
NEVER
Maximum duration under short overload condition (typically 3s)
Inv Time Aiming Point
0348
Parameters::Motor Control::Stack Inv
Time
105.00
0.00 to 125.00
%
ALWAYS
Current in % where the power stack can undertake the load current permanently
Inv Time Output
0349
Parameters::Motor Control::Stack Inv
Time
x.
0 to 500
%
NEVER
Actual output current limit as a % of the stack current
Inv Time Up Rate
0350
Parameters::Motor Control::Stack Inv
Time
5.000
0.000 to 120.000
s
STOPPED
Ramp value to ramp up current when overload condition disappears
Inv Time Down Rate
0351
Parameters::Motor Control::Stack Inv
Time
5.000
0.000 to 120.000
s
STOPPED
Ramp value to reach the aiming point under prolonged overload condition
Inv Time Warning
0352
Parameters::Motor Control::Stack Inv
Time
NEVER
The protection starts to integrate overload conditions
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...