Parameter Reference
D-205
AC30 series Variable Speed Drive
PNO Name
Path
Type
Default
Range
Units
WQ
View
Notes MBus
0361 Slew Rate Accel Limit
Parameters::Motor Control::Slew Rate
REAL
500
1 to 1200
Hz/s
ALWAYS TECHNICIAN
01249
0362 Slew Rate Decel Limit
Parameters::Motor Control::Slew Rate
REAL
500
1 to 1200
Hz/s
ALWAYS TECHNICIAN
01251
0364 Stabilisation Enable
Parameters::Motor Control::Stabilisation
BOOL
TRUE
ALWAYS TECHNICIAN
01255
0371 Terminal Voltage Mode
Parameters::Motor Control::Voltage Control
USINT
(enum)
0
0:NONE
1:FIXED
2:AUTOMATIC
ALWAYS TECHNICIAN
01269
0374 Motor Base Volts
Parameters::Motor Control::Voltage Control
REAL
100.00
0.00 to 115.47
%
ALWAYS TECHNICIAN
01275
0380 Power kW
Monitor::Energy Meter
Parameters::Motor Control::Energy Meter
REAL
x.xx
0.00 to 1000000.00
kW
NEVER
TECHNICIAN
01287
0381 Power HP
Same as PNO 380
REAL
x.xx
0.00 to 1000000.00
HP
NEVER
TECHNICIAN
01289
0382 Reactive Power
Same as PNO 380
REAL
x.xx
0.00 to 1000000.00
kVAr
NEVER
TECHNICIAN
01291
0383 Energy kWh
Same as PNO 380
REAL
x.xx
0.00 to 10000000.00
kWh
NEVER
TECHNICIAN 1
01293
0385 Power Factor Est
Same as PNO 380
REAL
x.xx
0.00 to 1.00
NEVER
TECHNICIAN
01297
0386 Power Factor Angle Est
Parameters::Motor Control::Energy Meter
REAL
x.xx
0.00 to 90.00
deg
NEVER
TECHNICIAN
01299
0389 Reset Energy Meter
Parameters::Motor Control::Energy Meter
BOOL
FALSE
ALWAYS TECHNICIAN 2
01305
0390 Duty Selection
Setup::Motor Control::Control and Type
Parameters::Motor Control::Feedbacks
USINT
(enum)
1
0:HEAVY DUTY
1:NORMAL DUTY
STOPPED TECHNICIAN
01307
0392 DC Link Voltage
Monitor::Motor and Drive
Monitor::Regen Control
Parameters::Motor Control::Feedbacks
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01311
0393 Actual Speed RPM
Monitor::Motor and Drive
Parameters::Motor Control::Feedbacks
REAL
x.xx
-100000.00 to 100000.00
RPM
NEVER
TECHNICIAN
01313
0394 Actual Speed rps
Same as PNO 393
REAL
x.xx
-1500.00 to 1500.00
rev/s
NEVER
TECHNICIAN
01315
0395 Actual Speed Percent
Same as PNO 393
REAL
x.xx
-200.00 to 200.00
%
NEVER
OPERATOR
01317
0396 DC Link Volt Filtered
Same as PNO 393
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01319
0397 id
Parameters::Motor Control::Feedbacks
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01321
0398 iq
Parameters::Motor Control::Feedbacks
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01323
0399 Actual Torque
Same as PNO 393
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01325
0400 Actual Field Current
Same as PNO 393
REAL
x.x
-200.0 to 200.0
%
NEVER
TECHNICIAN
01327
0401 Motor Current Percent
Same as PNO 393
REAL
x.x
0.0 to 500.0
%
NEVER
TECHNICIAN
01329
0402 Motor Current
Same as PNO 393
REAL
x.x
0.0 to 2000.0
A
NEVER
TECHNICIAN
01331
0403 100% Stack Current A
Parameters::Motor Control::Feedbacks
REAL
x.x
0.0 to 500.0
A
NEVER
TECHNICIAN
01333
0404 Stack Current (%)
Parameters::Motor Control::Feedbacks
REAL
x.
0 to 500
%
NEVER
TECHNICIAN
01335
0405 Motor Terminal Volts
Same as PNO 393
REAL
x.
0 to 1000
V
NEVER
TECHNICIAN
01337
0406 CM Temperature
Same as PNO 393
REAL
x.x
-25.0 to 200.0
°C
NEVER
TECHNICIAN
01339
0407 Heatsink Temperature
Same as PNO 393
REAL
x.x
-25.0 to 200.0
°C
NEVER
TECHNICIAN
01341
0408 Elec Rotor Speed
Parameters::Motor Control::Feedbacks
REAL
x.x
-1500.0 to 1500.0
Hz
NEVER
OPERATOR
01343
0410 Archive Flags
Parameters::Application::App Info
WORD
NEVER
OPERATOR
01347
0412 Stack Frequency
Parameters::Motor Control::Pattern Generator
REAL
4.00
2.00 to 16.00
kHz
ALWAYS ENGINEER
6
01351
0413 Random Pattern IM
Parameters::Motor Control::Pattern Generator
BOOL
TRUE
ALWAYS ENGINEER
01353
0414 Deflux Delay
Parameters::Motor Control::Pattern Generator
TIME
1.000
0.000 to 10.000
s
STOPPED ENGINEER
6
01355
0415 Positive Torque Lim
Parameters::Motor Control::Torque Limit
REAL
150.0
-300.0 to 300.0
%
ALWAYS TECHNICIAN
01357
0416 Negative Torque Lim
Parameters::Motor Control::Torque Limit
REAL
-150.0
-300.0 to 300.0
%
ALWAYS TECHNICIAN
01359
0417 Main Torque Lim
Setup::Motor Control::Control and Type
Parameters::Motor Control::Torque Limit
REAL
150.0
0.0 to 300.0
%
ALWAYS TECHNICIAN
01361
0418 Fast Stop Torque Lim
Parameters::Motor Control::Torque Limit
REAL
150.0
0.0 to 300.0
%
ALWAYS TECHNICIAN
01363
0419 Symmetric Torque Lim
Parameters::Motor Control::Torque Limit
BOOL
FALSE
ALWAYS TECHNICIAN
01365
0420 Actual Pos Torque Lim
Monitor::Motor and Drive
Parameters::Motor Control::Torque Limit
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01367
0421 Actual Neg Torque Lim
Same as PNO 420
REAL
x.x
-500.0 to 500.0
%
NEVER
TECHNICIAN
01369
0422 VHz Shape
Setup::Motor Control::Control and Type
Parameters::Motor Control::Fluxing VHz
USINT
(enum)
0
0:LINEAR LAW
1:FAN LAW
2:USER DEFINED
3:APPLICATION DEFINED
STOPPED TECHNICIAN
01371
0423 VHz User Freq
Parameters::Motor Control::Fluxing VHz
ARRAY[0..10]
STOPPED ENGINEER
01373
0424 VHz User Freq[0]
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 100.0
%
STOPPED ENGINEER
01375
0425 VHz User Freq[1]
Parameters::Motor Control::Fluxing VHz
REAL
10.0
0.0 to 100.0
%
STOPPED ENGINEER
01377
0426 VHz User Freq[2]
Parameters::Motor Control::Fluxing VHz
REAL
20.0
0.0 to 100.0
%
STOPPED ENGINEER
01379
0427 VHz User Freq[3]
Parameters::Motor Control::Fluxing VHz
REAL
30.0
0.0 to 100.0
%
STOPPED ENGINEER
01381
0428 VHz User Freq[4]
Parameters::Motor Control::Fluxing VHz
REAL
40.0
0.0 to 100.0
%
STOPPED ENGINEER
01383
0429 VHz User Freq[5]
Parameters::Motor Control::Fluxing VHz
REAL
50.0
0.0 to 100.0
%
STOPPED ENGINEER
01385
0430 VHz User Freq[6]
Parameters::Motor Control::Fluxing VHz
REAL
60.0
0.0 to 100.0
%
STOPPED ENGINEER
01387
0431 VHz User Freq[7]
Parameters::Motor Control::Fluxing VHz
REAL
70.0
0.0 to 100.0
%
STOPPED ENGINEER
01389
0432 VHz User Freq[8]
Parameters::Motor Control::Fluxing VHz
REAL
80.0
0.0 to 100.0
%
STOPPED ENGINEER
01391
0433 VHz User Freq[9]
Parameters::Motor Control::Fluxing VHz
REAL
90.0
0.0 to 100.0
%
STOPPED ENGINEER
01393
0434 VHz User Freq[10]
Parameters::Motor Control::Fluxing VHz
REAL
100.0
0.0 to 100.0
%
STOPPED ENGINEER
01395
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...