![Parker AC30 series User Manual Download Page 497](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313497.webp)
Technical Specifications
F-2
AC30 series Variable Speed Drive
Typical example: 31V-4D0004-BF-2S0000 (as shown in the
“Example of Product Coding Scheme” on previous page).
This shows the product is an AC30V drive Frame D, IP21 standard suitable for fan and pump industry, rated at 400-480 Volts supply, 1.1kW (normal
duty), with brake switch fitted, and Category C2 EMC filter, with GKP fitted with standard conformal coating and no special options.
ENVIRONMENTAL DETAILS
Operating Temperature
NORMAL DUTY
HEAVY DUTY
Operating temperature is defined as the surrounding air temperature of the drive, when the drive and other equipment adjacent to
it is operating at worst case conditions.
0
C to 40
C, derate up to a maximum of 50
C
0
C to 45
C, derate up to a maximum of 50
C
Output power is derated linearly at 2% per degree centigrade for temperature exceeding the maximum rating for the drive.
Maximum operating temperature of the AC30D in the 24V dc supplied operating mode, without power applied to the stack, is 45
C.
Storage Temperature
-25
C to +55
C
Shipping Temperature
-25
C to +70
C
Product Enclosure Rating
IP20
– remainder of surfaces (Europe)
With frame sizes H & J, in order to retain the IP20 rating when making use of the DC-bus terminals, only partly remove DC-bus
terminal cover breakouts or use additional external guarding.
UL (c-UL) Open Type (North America/Canada)
Cubicle Mounted
IP20
UL (c-UL) Open Type (North America/Canada)
Through-panel Mounted
IP20
UL (c-UL) Open Type (North America/Canada)
Altitude
If greater than 1000m above sea level, derate by 1% per 100m to a maximum of 2000m
Humidity
Maximum 85% relative humidity at 40
C non-condensing
Atmosphere
Non flammable, non corrosive and dust free
Climatic Conditions
Class 3k3, as defined by EN60721-3-3
Chemically Active Substances
For the standard product (which inherently includes our optimal level of conformal coating) compliance with EN60721-3-3 is as
follows
–
a) Both classes 3C3 and 3C4 for hydrogen sulphide gas (H
2
S) at a gas concentration of 25ppm for 1200 hours.
b) Both classes 3C1 (rural) and 3C2 (urban) for all nine defined substances as defined in table 4.
Classes 3C1 and 3C2 are valid for both storage and transportation purposes.
Note - Product was tested and validated with a hydrogen sulphide environment of 25ppm for a continuous period of 1200 hours
and validated throughout the test period without failure.
Vibration
Test Fc of EN60068-2-6
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude
57Hz<=f<=150Hz sinusoidal 1g
10 sweep cycles per axis on each of three mutually perpendicular axis
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...