Parameter Reference
D-15
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
AR Initial Delay
1505
Same as PNO 1502
10.000
0.000 to 3600.000
s
ALWAYS
The timein seconds for which the AR feature will wait before attempting to restart the drive for the first restart attempt, (
1509 AR
Restarts Remaining
equals
1471 AR Max Restarts
). The delay time is started once all trips have become inactive.
The delay time is ignored if the AR feature is configured to simply reset the trip without attempting to restart the motor.
AR Repeat Delay
1506
Same as PNO 1502
60.000
0.000 to 3600.000
s
ALWAYS
The time in seconds for which the AR feature will wait before attempting to restart the drive for the second and subsequent restart
attempts, (
1509 AR Restarts Remaining
is not equal to
1471 AR Max Restarts
). The delay time is started once all trips have become
inactive.
The delay time is ignored if the AR feature is configured to simply reset the trip without attempting to restart the motor.
AR Trip Mask B
1734
Parameters::Motor Control::Auto
Restart
00000000
ALWAYS
AR Trip Mask 2 B
1735
Parameters::Motor Control::Auto
Restart
00000000
ALWAYS
AR Initial Delay B
1736
Parameters::Motor Control::Auto
Restart
60.000
0.000 to 3600.000
s
ALWAYS
AR Repeat Delay B
1737
Parameters::Motor Control::Auto
Restart
120.000
0.000 to 3600.000
s
ALWAYS
The ‘B’ parameters define a second set of trips and associated restart delays. This set operates in parallel with the primary set. If a trip
is enabled in both sets, the restart time associated with the primary set, (A), will apply.
Typically use of the ‘B’ set of trips will be to configure some trips to cause a delayed restart action, while the primary set of trips may be
acted on with a shorter delay.
AR Active
1507
Parameters::Motor Control::Auto Restart
NEVER
Indicates that the AR feature will reset the trip source once all trips have become inactive, (following a delay time if the AR feature has
been configured to also restart the motor).
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...