![Parker AC30 series User Manual Download Page 429](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313429.webp)
Parameter Reference
D-169
AC30 series Variable Speed Drive
Speed Ref
Parameters::Motor control::Speed Ref
This function holds all the parameters concerning the generation of the setpoint reference (reference ramp, speed trim, setpoint reverse, etc.).
Parameter Name
No.
Path
Default
Range
Units
Writable
Ref Min Speed Clamp
1264
Parameters::Motor Control::Speed Ref
-110.00
-110.00 to 0.00
%
ALWAYS
Minimum value for
Ramp Speed Output
Ref Max Speed Clamp
1265
Parameters::Motor Control::Speed Ref
110.00
0.00 to 110.00
%
ALWAYS
Maximum value for
Ramp Speed Output
Ref Speed Trim
1266
Parameters::Motor Control::Speed Ref
0.00
-300.00 to 300.00
%
ALWAYS
The trim is added to the ramp output to form the
Ramp Speed Output
(unconditionally in remote mode).
In local mode, it is added is the
Ref Trim Local
parameter is set to TRUE
Ref Trim Local
1267
Parameters::Motor Control::Speed Ref
FALSE
ALWAYS
When TRUE, the trim is added to the ramp output in local mode.
When FALSE, the trim is not added to the ramp output in local mode.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...