A-11
Modbus TCP
AC30 series Variable Speed Inverter
1458
Modbus Conn Timeout
Type: TIME
Default: 66 seconds
Base Communications Modbus TCP parameter.
Sets the Modbus connection timeout. If this parameter is set to zero then the connection will not timeout.
Range
Writable Saved Config
0
…
100 000 seconds
1567
Modbus Mapping
Type: Array of UINT
Default: none
Base Communications Modbus TCP parameter.
User-defined Modbus parameter mapping table. Each entry in the table represents the required parameter number.
Range
Writable Saved Config
0
…
Last parameter number.
1632
Mapping Valid
Type: BOOL
Base Communications Modbus TCP parameter.
Status of the user defined mapping area. This will be set to TRUE if all entries in the mapping table are valid.
Range
Writable Saved Config
FALSE
TRUE
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...