![Parker AC30 series User Manual Download Page 357](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313357.webp)
Parameter Reference
D-97
AC30 series Variable Speed Drive
Local Control
Parameters::Keypad::Local Control
These parameters configure the use of the GKP keys for local start / stop control of the drive.
Parameter Name
No.
Path
Default
Range
Units
Writable
Run Key Action
1140
Parameters::Keypad::Local Control
0
0:RUN
1:JOG
STOPPED
Defines the use of the green run key in local mode.
When RUN is selected, pressing the green Run key will start the drive using Local Reference as the active setpoint. To stop the drive
press the RED Stop key.
When JOG is selected, pressing the green Run key will start the drive running using the Jog Setpoint as the active setpoint. The drive
will stop when the key is released.
Local/Rem Key Active
1253
Parameters::Keypad::Local Control
TRUE
ALWAYS
Enables the L/R soft key function. This is used to change between Local and Remote sequencing modes from the GKP.
Local Dir Key Active
1255
Parameters::Keypad::Local Control
TRUE
ALWAYS
Enables the ability to change the direction from the GKP when running in local sequencing mode. When FALSE the direction will
always be positive.
Local Run Key Active
1239
Parameters::Keypad::Local Control
TRUE
ALWAYS
Enables the green Run key function when in local sequencing mode. When FALSE the Run key is ignored, (for both RUN and JOG
modes).
Local Reverse
1240
Parameters::Keypad::Local Control
FALSE
ALWAYS
Used to change the direction the motor will rotate when in local sequencing mode. When FALSE the direction will be “Forwards”. When
TRUE the direction will be reverse.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...