Runtime Alerts
A Runtime Alert is a fault that indicates a permanent hardware error. The Runtime Alert display is of the form
RUNTIME ALERT
CODE 00000000 xx
CODE is a number in the range 0 to 65000. The following value is used to provide additional information to assist Parker Hannifin Technical
Support personnel.
CODE
ERROR
Possible Reason for Error
1 to
255
Internal exception
VCM not secured to power stack
Option not secured correctly to VCM control card
Earth bonding failure.
Fault during firmware upgrade
12
Memory access
Attempt to read or write to protected memory. Most likely this will be due to a configuration error. Press OK
several times until the drive resets correctly, then replace the configuration using PDQ.
Record the error message and contact Technical Support
1001
to
1003
Processor overload
Select a lower switching frequency, (
Parameters::Motor Control::Pattern Generator::Stack Frequency)
Record the error message and contact Technical Support
1006
Memory overflow
Reduce the complexity of the application
Reduce the number of parameters being accessed via the on board Modbus TCP protocol
Reduce the number of parameters being accessed by the fieldbus communications option.
1007
Uninitialized pointer
Record the error message and contact Technical Support
1010,
1101
to
1113
Initialization error
Record the error message and contact Technical Support
1200
to
1299
Communications option
error
Ensure the communications option is correctly fitted
Update the firmware in the inverter.
Replace the communications option
1300
Ethernet fault
Record the error message and contact Technical Support
1301
Modbus server
Record the error message and contact Technical Support
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...