![Parker AC30 series User Manual Download Page 267](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313267.webp)
Parameter Reference
D-7
AC30 series Variable Speed Drive
Line Synchronisation
Typically the system will contain an AC30P/AC30D regen drive providing 4-Q power supply, and one or more drives on the common DC bus.
However, in order for the AFE control procedures to operate correctly, a synchronization of the IGBT firing sequence to the three phase mains
supply voltage frequency, angle, and direction of rotation need to be performed. This is achieved by using a line sync card (LA471892U001),
connected to a standard AC30 encoder option board (7004-04-00). Failure to successfully synchronise could cause significant supply distortion, poor
power factor, or even catastrophic failure.
AFE Parameter List
The full set of AFE related parameters are given in a table below:
Parameter Name
No.
Path
Default
Range
Units
Writable
AFE Inductance
1730
Setup::Regen Control
Parameters::Regen Control::AFE
0.00
0.00 to 1000.00
mH
ALWAYS
Total inductance (3% + 5%) from the LCL filter in the AFE configuration.
AFE PF Angle Demand
1693
Parameters::Regen Control::AFE
0.00
-90.00 to 90.00
deg
ALWAYS
Sets AFE in current control mode (TRUE) or leaves it in voltage control mode (FALSE).
AFE Id Demand
1705
Same as PNO 1693
0.10
-1.50 to 1.50
ALWAYS
Iq current demand. Set directly in both current control mode, or voltage control mode.
AFE Id Demand
1704
Same as PNO 1693
0.10
-1.50 to 1.50
ALWAYS
Id current demand. Set directly only in current control mode. In voltage control mode set by dc link voltage loop.
AFE Max Current
1706
Parameters::Regen Control::AFE
1.50
0.00 to 1.50
ALWAYS
Maximum allowed current in AFE mode.
AFE Close Ext PCR
1690
Parameters::Regen Control::AFE
FALSE
ALWAYS
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...