Parameter Reference
D-129
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Pwrl Decel Rate
1649
Parameters::Motor Control::Power Loss
Ride Thru
100
1 to 500
Hz/s
STOPPED
Rate in Hz/s ( electrical frequency/ second) at which the speed septoint is ramped to Zero
If this value is set too low, then the deceleration will may be not enough high for having regenerative condition to maintain the dc link.
Pwrl Time Limit
1650
Parameters::Motor Control::Power Loss
Ride Thru
30.000
0.000 to 300.000
s
STOPPED
Maximum allowed time in second of the Power Loss Ride Through sequence
If this value is reached, the the drive will trip on POWER LOSS STOP.
Pwrl Active
1651
Parameters::Motor Control::Power Loss
Ride Thru
NEVER
This diagnostic is TRUE while the Power Loss Ride Through is active
Functional Description
When
Pwrl Enable
is set to TRUE, the block controls the behaviour of the drive during a power outage.
This is achieved by ramping the speed setpoint to zero(
Pwrl Decel Rate
).
The dc link fall detection is triggered by
Pwrl Trip Threshold. Pwrl Control Band
determines the band of dc link ( between by
Pwrl Trip
Threshold
and
Pwrl trip Thr Pwrl Control Band
) while the speed septoint is ramped down to zero using
Pwrl Decel Rate
to try
recovering the kinetic energy.
If during the outage the supply returns, the speed is automatically ramped back (
Pwrl Accel Rate
) to the speed setpoint.
The condition to validate the supply returns is met if the dc link is kept higher than (
Pwrl trip Thr Pwrl Control Band
) for more than
500ms. During this time, the speed setpoint is hold.
Pwrl Time Limit
determines the maximum time of the Power Loss Ride Through sequence. If this time is exceeded, the drive will trip on POWER
LOSS STOP.
During the Power Loss Ride Through sequence,
Pwrl Active
becomes TRUE
.
When
Pwrl Enable
is set to FALSE, the drive will trip on UNDERVOLTS if the main supply is removed.
This feature is run at a rate of 1 milli-second.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...