![Parker AC30 series User Manual Download Page 498](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313498.webp)
F-3
Technical Specifications
AC30 series Variable Speed Drive
Safety
Overvoltage Category
Overvoltage Category III (numeral defining an impulse withstand level)
Pollution Degree
Pollution Degree II (non-conductive pollution, except for temporary condensation) for control electronics
Pollution Degree III (dirty air rating) for through-panel mounted parts
North America/Canada
Complies with the requirements of UL508C as an open-type drive.
EARTHING/SAFETY DETAILS
Earthing
Permanent earthing is mandatory on all units.
Use a copper protective earth conductor 10mm² minimum cross-section, or install a second conductor in parallel with the
protective conductor to a separate protective earth terminal
The conductor itself must meet local requirements for a protective earth conductor
Input Supply Details
(TN) and (IT)
Drives without filters are suitable for earth referenced (TN) or non-earth referenced (IT) supplies.
The drive is only suitable for earth referenced supplies (TN) when fitted with an internal filter. External filters are available for use
on TN and IT (non-earth referenced) supplies.
Prospective Short Circuit
Current (PSCC)
Refer to the appropriate Electrical Ratings table.
Earth Leakage Current
>10mA (all models)
COOLING FANS
The forced-vent cooling of the drive is achieved by 1, 2 or in some cases 3 fans. The Fan Rating gives the volume of air venting from the drive per fan.
Product
Main Cooling Fan Ratings
Internal Cooling Fan Ratings
FRAME D
Above 2.2kW only
1 off 27 cfm (45m³/hr)
FRAME E
All models
1 off 33 cfm (56m³/hr)
FRAME F
All models
2 off 27 cfm (45m³/hr)
FRAME G
All models
2 off 53 cfm (89 m³/hr)
1 off 27 cfm (45 m³/hr)
FRAME H
45kW
2 off 27 cfm (45 m³/hr)
1 off 27 cfm (45 m³/hr)
55
– 75kW
2 off 53 cfm (89 m³/hr)
FRAME J
All Models
3 off 80 cfm (133 m³/hr)
2 off 27 cfm (45 m³/hr)
FRAME K
All models
1 off 518 cfm (880 m³/hr)
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...