308
Absolute Encoder Origin
Section 8-6
8-6-3
PCU Data Settings for Using Absolute Encoders
The parameters and data required when using absolute encoders are as fol-
lows:
Axis Parameter Area
The following parameters are for the operation mode for origin searches.
d = 1860 hex + (Axis No.
−
1)
×
14 hex
When using an absolute encoder, make sure that the settings for the encoder
type in the Axis Parameters and
Operation Switch When Using Absolute
Encoder
in the Servo Parameters match.
If the settings do not match, reading absolute data will not be possible, or
another malfunction may occur.
Servo Parameter Area
Parameters for Using G-series Absolute Encoders
PCU's
address
Contents
Setting
15 to 12
11 to 08
07 to 04
03 to 00
d+2
0 (fixed)
0 (fixed)
0 (fixed)
Encoder type
0: Incremental encoder (default setting)
1: Absolute encoder
Axis Parameter
Area
Encoder type
G-series Servo Parameter Pn00B
(Operation switch when using absolute encoder)
0: Use as an absolute
encoder.
2: Use as an absolute
encoder but ignore abso-
lute multi-turn counter over-
flow alarm.
1: Use as an incremental
encoder.
0: Incremental
encoder
Do not set this combination.
This setting is used when
using an absolute encoder as
an incremental encoder
1: Absolute encoder
This setting is used when
using an absolute encoder as
an absolute encoder.
(Set this combination when
using an absolute encoder.)
Do not set this combination.
Axis Parameter
Area
Encoder type
W-series Servo Parameter Pn002.2
(Operation switch when using absolute encoder)
0: Use as absolute encoder.
1: Use as incremental
encoder.
0: Incremental
encoder
Do not set this combination.
This setting is used when
using an absolute encoder as
an incremental encoder
1: Absolute encoder
This setting is used when
using an absolute encoder as
an absolute encoder.
(Set this combination when
using an absolute encoder.)
Do not set this combination.
Type
Parameter
No.
Parameter name
Unit
Setting
range
Parameter
size
Default
setting
---
Pn00B
Operation switch when using absolute
encoder
---
0 to 2
2
0
Summary of Contents for CJ1W-MA - REV 10-2008
Page 3: ...iv ...
Page 5: ...vi ...
Page 21: ...xxii ...
Page 57: ...30 Starting Operation Section 2 2 ...
Page 97: ...70 Wiring Section 3 4 ...
Page 247: ...220 Transferring Servo Parameters Section 5 3 ...
Page 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Page 343: ...316 Absolute Encoder Origin Section 8 6 ...
Page 375: ...348 Linear Interpolation Section 9 7 ...
Page 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Page 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Page 641: ...614 Index ...
Page 643: ...616 Revision History ...