Product Features
83
© 2017, ATEÏS, member of PAX ProAV Group
Text messages display on the touch screen of IDA8C:
"URGP 32I Fault"
"Port:1 IP:1, ch1 Short", where Port N is the Nth PDC port for a peripheral connection.
The IP is the unique number for each peripheral device on the PDC port, ch is the
number of the channel.
A text message displays at the window [Machine Fault Record] in Ateis Studio:
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Fault Handling : URGP Fault
3.1.9.1.16 Remote Fault
An error is detected on peripheral devices. For PPM-AS or PSS-AS, this fault relates to a capsule
microphone or a speaker error.
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log
o
PPM-AS / PSS-AS Capsule Microphone Open or Short / Speaker Error:
The text messages display on the touch screen of IDA8C:
"Remote Fault"
"PSS Port:1 ID:1, Microphone Fault", where Port N is the Nth PDC port for a peripheral
connection. The ID is the unique number for each peripheral device on the PDC port.
A text message displays at the window [Machine Fault Record] in Ateis Studio: