IDA8 Global-Net User Manual
138
© 2017, ATEÏS, member of PAX ProAV Group
.1.3.6.1.4.1.30512.2.12.1.4
UserFaultStatus
Content
Details
W atchdogCounter
The counter will increase ev ery 8 seconds.
Author
ATEIS Group
Product
IDA8C
SystemTicks
System running time (ms)
Version
Version 2
Status
System Global Status
Bit15 = Minor Fault
Bit14 = Major Fault
Bit13 = Primary activ e if RU config
Bit12 = Secondary activ e if RU config
Bit11 = Backup dev ice fault if RU config
Bit10 = Ethernet cable broken
Bit9 = Ev acuation
Bit8 = NTP serv er disconnection
Bit7 = System Fault
Bit6 = Local ATEIS Net Backup Mode
Bit5 = Local ATEIS Net Broken
Bit4 = Global ATEIS Net Backup Mode
Bit3 = Global ATEIS Net Broken
Bit2 = Bypass Mode
NumLines
The number of speaker line in the system. If there are 5 IDA8 units, the number of line is 8 x 5 = 40 lines.
Lines
The Speaker Line Monitoring
Line
Line Class: Each IDA8 unit has 8 lines (zones).
Node 1 ~ 8 = 1st IDA8
Node 9 ~ 16 = 2nd IDA8
Node 17 ~ 24 = 3rd IDA8
Node 25 ~ 32 = 4th IDA8 ...and so on.
If configured the system with ATEIS Global-Nets, the order will local net first, then global net. For example, the system
network is: IDA8C(1, 1), IDA8S(1, 2), IDA8S(1, 3), IDA8C(2, 1), IDA8S(2, 2), IDA8C(3, 1).
Node 1 ~ 8 = IDA8 (1, 1) Line 1~8
Node 9 ~ 16 = IDA8 (1, 2) Line 1~8
Node 17 ~ 24 = IDA8 (1, 3) Line 1~8
Node 25 ~ 32 = IDA8 (2, 1) Line 1~8
Node 33 ~ 40 = IDA8 (2, 2) Line 1~8
Node 41 ~ 48 = IDA8 (3, 1) Line 1~8
LineIndex
Line Index uniquely, from 1 to N.
LineMajorFault
1 if major fault, 0 if normal.
The conditions include:
1. Open Circuit
2. Short Circuit
3. Bad Impedance
4. Do Not Get Backup AMP
5. IDA8 Unit Offline
LineMinorFault
1 if minor fault, 0 if normal.
The conditions include:
1. Line Leakage
2. Normal AMP Fault, but backup AMP
3. Only Backup AMP Fault
LineOpenFault
1 if open circuit, 0 if normal.
LineShortFault
1 if short circuit, 0 if normal.
LineImpFault
1 if bad impedance by 18/20KHz monitoring, 0 if normal.
LineImp1kFault
1 if bad impedance by 1KHz monitoring, 0 if normal.
LineLeakFault
1 if leakage, 0 if normal.
LineAmpFault
1 if Normal AMP Fault, 0 if normal.
LineAmpBackupFault
1 if Backup AMP Fault, 0 if normal.
NumRemotes
The number of PDC port in the system.
IDA8C series fix 4 PDC Port.
IDA8S series fix 2 PDC Port.
For example, there are 2 IDA8C and 5 IDA8S, the number of PDC port is 2 x 4 + 5 x 2 = 18.
Remotes
Remote(PDC) Port Status
Remote
Remote Status Class: Must connect RS485 Input to NPC in the configuration, then set Modbus Type to Peripheral Input
and set Modbus Channel uniquely in the NPC. The node order will follow Modbus Channel.
For example, set the1st IDA8C on Modbus Channel 1~4 for PDC 1~4, set the 2nd IDA8S on Modbus Channel 5~6 for PDC
1~2, the node order will be:
Node 1 ~ 4 = 1st IDA8C PDC 1~4.
Node 5 ~ 6 = 2nd IDA8C PDC 1~2 ...and so on.
If the system net config are: IDA8C(1, 1), IDA8S(1, 2), IDA8S(1, 3), IDA8C(2, 1), IDA8S(2, 2), IDA8C(3, 1).
Node 1 ~ 4 = IDA8C (1, 1) PDC 1~4
Node 5 ~ 6 = IDA8S (1, 2) PDC 1~2
Node 7 ~ 8 = IDA8S (1, 3) PDC 1~2
Node 9 ~ 12 = IDA8C (2, 1) PDC 1~4
Node 13 ~ 14 = IDA8S (2, 2) PDC 1~2
Node 14 ~ 18 = IDA8C (3, 1) PDC 1~4
RemoteIndex
Remote(PDC) Index uniquely, from 1 to N.
RemoteAbsentFault
If the Modbus Channel in this Index will not be set, the v alue is 0.
If sets the Modbus Channel:
The v alue is 1 if the remote is offline.
The v alue is 2 if the remote is online.
The v alue is 1 if the IDA8 unit is offline.
RemoteMicFault
If sets Modbus Channel:
The v alue is 1 if the microphone has fault.