IDA8 Global-Net User Manual
152
© 2017, ATEÏS, member of PAX ProAV Group
This LED lights up if active system is secondary audio processor.
Fault Indicator:
This LED lights up if the unit is set to be slave, and a short or open is detected on S. WD (Secondary
Watching Dog) port.
If this indicator lights up, it means there is an error of the unit, user needs to check wiring of S.
WD connector or replace by a good unit.
Power Indicator:
This LED lights up if this unit is powered.
3.2.1.2.2 Rear Panel
Output Contacts:
There are 8 channels for output contacts, each channel consist of three connectors, where "N" is the
number of channel:
P_N: Connect to Nth output contact of primary audio processor.
N: Nth channel of output contact.
S_N: Connect to Nth output contact of secondary audio processor.
Expansion Power Supply:
Output 24V DC power to next RU-MAIN/PDC/CTL devices.
There are two connectors of this output:
PRI: Connect to Power Supply PRI connector next RU-MAIN/PDC/CTL.
SEC: Connect to Power Supply SEC connector next RU-MAIN/PDC/CTL.
Power Supply:
24V DC power input, which is connect to 24V DC Output of audio processor.
There are two connectors of this input:
PRI: 24V DC power input from primary audio processor.
SEC: 24V DC power input from secondary audio processor.
Evacuation Inputs:
There are 9 channels for evacuation input, each channel consist of three connectors, where "N" is the
number of channel:
P_N: Connect to Nth evacuation input of primary audio processor.
N: Nth channel of evacuation input.
S_N: Connect to Nth evacuation input of secondary audio processor.
Active Control Expansion Output:
This port output logic signal to next RU devices to synchronize redundancy state which tells primary