Product Features
307
© 2017, ATEÏS, member of PAX ProAV Group
The unit comprises of 16 zones/16 buttons with Fireman microphone in a metal surface mount wall-box.
It provides robust IP-30 protection. Each PCP contains a PMM PS Master PCB with extension keypad and
uses the same architecture as for the PPM-AS series of microphone consoles. Each ATEIS audio processor
is capable to support up to 32 x PCP units per RS485 port in Master/Slave configuration.
The control buttons represent a single zone or a group of zones. All buttons can be [re-programmed from
Ateis Studio, The PTT button can be programmed for Push To Talk function or for latching functionality.
The unit offers “Hold” and “Busy” LED signals in addition to the zone LED’s, and these features allow an
easy identification of Selection/Busy signals for users. In addition, to meet the compliance with EN 54-16,
POWER, FAULT and EVAC indicators are provided with.
3.2.18.1 Control Panel
A telephone styled microphone for paging.
Busy Indicator(1~8):
Show the status of zone:
Color
Status
Frequency
Activity
Red
Permanent
Priority of the zone is lower than other sources.
Green
Blinking
°
°
Priority of the zone is higher than other sources.
Green
Permanent
The zone only desired for paging is not using by other
sources.
Fault Indicator:
To display fault status of system. The following table lists the states of fault:
Status
Frequency
Activity
Permanent
There are faults in audio processor.
Blinking
°
°
Lost communication with audio processor.
EVAC Indicator:
Light up when the system is under evacuation paging.
Status
Frequency
Activity
Permanent
System is under evacuation paging.
Blinking
°
°
PCP does not do a "Plug-in" in Ateis Studio before using.
Power Indicator:
Light up when the PCP is powered on.