IDA8 Global-Net User Manual
72
© 2017, ATEÏS, member of PAX ProAV Group
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Troubleshooting: Check the component which is the input of "Fault Definer", and re-define its
configuration.
3.1.9.1.3 PDC Error
The audio cable for Fireman and PDC port turns short circuit or cuts off.
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log:
A text message displays on the touch screen of IDA8C:
o
"PDC Error"
The text messages display at the window [Machine Fault Record] in Ateis Studio:
o
PDC: Indicates errors in which PDC port.
o
Audio Short: Turns short circuit.
Troubleshooting: Check the audio cable.
3.1.9.1.4 Normal Amplifier Error
Amplifier gain is too high/Amplifier gain is too low/Amplifier has failed.
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
o
Zone Fault LEDs on the front panel of the IDA8C/S.
Log:
o
Amplifier Gain too High/Low/Amplifier Fail:
The text messages display at touch screen on the front panel of IDA8C:
"Normal AMP Error" or "Backup AMP Error".
"Z1 Normal AMP Too High", where "Z1" could be any other zones, and "Normal AMP"
could be "Backup AMP" as well.
A text message displays at the [Machine Fault Record] window in the Ateis Studio:
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Troubleshooting: